In Advantech DiagAnywhere Server, Versions 3.07.11 and prior, multiple stack-based buffer overflow vulnerabilities exist in the file transfer service listening on the TCP port. Successful exploitation could allow an unauthenticated attacker to execute arbitrary code with the privileges of the user running DiagAnywhere Server.
In Advantech WebAccess/HMI Designer 2.1.9.31, Data from a Faulting Address controls Code Flow starting at PM_V3!CTagInfoThreadBase::GetNICInfo+0x0000000000512918.
Advantech WebAccess/HMI Designer 2.1.9.31 has a User Mode Write AV starting at MSVCR90!memcpy+0x000000000000015c.
In WebAccess versions 8.4.1 and prior, multiple stack-based buffer overflow vulnerabilities are caused by a lack of proper validation of the length of user-supplied data. Exploitation of these vulnerabilities may allow remote code execution.
In WebAccess/SCADA Versions 8.3.5 and prior, multiple heap-based buffer overflow vulnerabilities are caused by a lack of proper validation of the length of user-supplied data. Exploitation of these vulnerabilities may allow remote code execution. Note: A different vulnerability than CVE-2019-10991.
In WebAccess/SCADA, Versions 8.3.5 and prior, multiple stack-based buffer overflow vulnerabilities are caused by a lack of proper validation of the length of user-supplied data. Exploitation of these vulnerabilities may allow remote code execution.
Stack-based buffer overflow in Advantech WebAccess/SCADA 8.4.0 allows a remote, unauthenticated attacker to execute arbitrary code by sending a crafted IOCTL 81024 RPC call.
Stack-based buffer overflow in Advantech WebAccess/SCADA 8.4.0 allows a remote, unauthenticated attacker to execute arbitrary code by sending a crafted IOCTL 10012 RPC call.
Advantech WebAccess/SCADA, Versions 8.3.5 and prior. Multiple stack-based buffer overflow vulnerabilities, caused by a lack of proper validation of the length of user-supplied data, may allow remote code execution.